Product Introduction
Intelligent instrument calibrator for PT CT error and impedance admittance test.It meets the requirements of JJG313-94 current transformer verification regulation and JJG314-94 voltage transformer verification regulation.
Product Characteristics
1、Intelligent transformer calibrator adopts 320 240 lattice liquid crystal, with large visual range and long life backlight, convenient to use
2、Chinese operation interface, beautiful interface
3、The percentage difference Angle difference is displayed in large font, which is convenient for users to observe
4、The intelligent transformer calibrator produced by our company fully meets the requirements of jjg314-1993 and jjg314-1994, and it can be sampled automatically
5、Automatically judge polarity error, change ratio error
6、The upper computer software has the open function of virtual instrument
7、Completely solve the s-level measurement problem
8、Automatic range switching
9、The perfect combination of advanced and unique circuit and DSP technology can completely remove the problem of the circuit instability
10、power dissipation:<15VA(No micro printer);<25VA(microprinter)
11、Harmonic suppression ratio:>40db
12、boundary dimension(Band dimensions):260×350×150mm3
13、weight:6kg
Parámetros técnicos
| Entorno operativo del equipo | temperature:5℃~40℃ | relative humidity:<80%(25℃) |
| altitude:<2500m | ||
| mains frequency:50Hz±0.5Hz | mains input:220V±5V | |
| rango de medida | cophase component(%):0.0001~200.0 | distinguishability:0.0001 |
| orthogonal component(part):0.001~700.0 | distinguishability:0.001 | |
| impedance(Ω):0.0001~20.0 | distinguishability:0.0001 | |
| admittance(ms):0.0001~20.0 | distinguishability:0.0001 | |
| error intrínseco | componente cofase | ΔX=±(X×2%+Y×2%)±Dx(Level 1 is optional) |
| componente ortogonal | ΔY=±(X×2%+Y×2%)±Dy(Level 1 is optional) | |
| "X"、"Y"——Display value of instrument | ||
| "Dx,Dy"——Display value of instrument | ||
| Dx=2,Dy=5 | ||
| indicador de cuadrante | PETS2 (El nivel 1 es opcional) | |
| Rango de trabajo | electricidad | (1%~149%)In (In =5A) |
| (5%~149%)In (In =1A) | ||
| Voltaje | (5%~149%)Un (Un =100V,150V,100V/) | |
| (5%~149%)Un (Un =100V/3) | ||
| carga de trabajo | electricidad | TO to TX<0.12Ω cosΦ=1 |
| Voltaje | a to x<0.25VA (100V) | |
| Indicación de error de polaridad | Cuando la corriente operativa (voltaje) alcanza más del 5% de la corriente nominal (voltaje) y el error excede el 180%, debe haber una indicación de polaridad. | |
| Nota: si es más del 10% de la corriente nominal de funcionamiento (voltaje), todavía no hay indicación de polaridad adecuada, lo que indica una falla. No aumente la corriente (voltaje) para evitar quemar el instrumento. | ||
| Indicación de error de relación variable | Cuando la corriente operativa (voltaje) alcanza más del 5% de la corriente nominal (voltaje) y el error excede el 30% pero es inferior al 180%, se debe dar la indicación de error de relación variable. | |
| Prueba de aislamiento y tensión y instrucciones | terminalTX( | |
| The power socket can withstand the housing1.5kV,1minwithstand voltage | ||