  • In the series resonance experiment, automatic tuning of the device cannot be achieved,the reason for not being able to find the resonance point

    The series resonance under UHV power can help many power workers conduct various power tests more conveniently.

    32

    Phenomenon:

    The tuning curve is a straight line, and the instrument indicates no resonance point after tuning

    reason:

    Poor grounding of the circuit, incorrect wiring of the testing circuit, and open circuit of the instrument and equipment

    Elimination method:

    1) Check if the grounding device is reliable and if the grounding connection wire is disconnected;

    2) Check the on/off status of the high and low voltage coils of the excitation transformer; (Low voltage winding resistance; high voltage winding resistance at each output end vs high voltage tail)

    3) Check the continuity of each reactor; (Resistance of each winding)

    4) Check the continuity of the voltage divider signal line; (High and low voltage capacity)

    5) Check the continuity of the high and low voltage capacitor arms of the voltage divider; (Core 1 hole, shell 2 holes; 1 hole is disconnected from 2 holes)

    6) The device itself does not have a resonance point for boosting, and it is necessary to check the continuity of the compensation capacitor;

    If all components are normal and there are still no resonance points, please contact the after-sales company and do not disassemble the instrument by yourself!

    También podría gustarte

    • ¡Tiene alguna pregunta!

      NO DUDE EN CONTACTARNOS EN CUALQUIER MOMENTO
      Contáctenos
    • Visítanos

      Edificio 6, Parque Industrial Óptico-Mecánico Optics Valley, 84 Gaoxin 5 Road,
      Zona de desarrollo de nuevas tecnologías de East Lake, ciudad de Wuhan, provincia de Hubei, China

    • Envíanos un correo electrónico

      qiao@hvtest.cc

    • Llámanos

      +86-15871365102