  • In the series resonance experiment, automatic tuning of the device cannot be achieved,the reason for not being able to find the resonance point

    The series resonance La energía UHV puede ayudar a muchos trabajadores de energía a realizar varias pruebas de energía de manera más conveniente.

    32

    Phenomenon:

    The tuning curve is a straight line, and the instrument indicates no resonance point after tuning

    reason:

    Poor grounding of the circuit, incorrect wiring of the testing circuit, and open circuit of the instrument and equipment

    Elimination method:

    1) Check if the grounding device is reliable and if the grounding connection wire is disconnected;

    2) Check the on/off status of the high and low voltage coils of the excitation transformer; (Low voltage winding resistance; high voltage winding resistance at each output end vs high voltage tail)

    3) Check the continuity of each reactor; (Resistance of each winding)

    4) Check the continuity of the voltage divider signal line; (High and low voltage capacity)

    5) Check the continuity of the high and low voltage capacitor arms of the voltage divider; (Core 1 hole, shell 2 holes; 1 hole is disconnected from 2 holes)

    6) The device itself does not have a resonance point for boosting, and it is necessary to check the continuity of the compensation capacitor;

    If all components are normal and there are still no resonance points, please contact the after-sales company and do not disassemble the instrument by yourself!

    También podría gustarte

    • ¡Tiene alguna pregunta!

      NO DUDE EN CONTACTARNOS EN CUALQUIER MOMENTO
      Contáctenos
    • Visítanos

      Edificio 6, Parque Industrial Óptico-Mecánico Optics Valley, 84 Gaoxin 5 Road,
      Zona de desarrollo de nuevas tecnologías de East Lake, ciudad de Wuhan, provincia de Hubei, China

    • Envíanos un correo electrónico

      qiao@hvtest.cc

    • Llámanos

      +86-15871365102