  • What is the difference between DC hipot and Megger?

    The DC hipot test Kit under Wuhan UHV can help many power workers conduct various power tests more conveniently.


    169


    1.DC Hipot Test

    Purpose: Verifies dielectric strength – the insulation’s ability to withstand high voltage without breaking down.

    Method: Applies a destructively high DC voltage (e.g., 2× to 10× operating voltage) to the insulation.

    Measurement: Monitors leakage current (µA/mA).

    Outcome: Pass/Fail (fails if current exceeds threshold or breakdown occurs).

    Risk: Potentially damages weak insulation. Critical safety step: Must discharge capacitive loads post-test.

    Use Cases:

    Safety certification (UL/IEC compliance).

    Production line quality checks.

    Detecting critical flaws (cracks, voids, thin spots).


    2.Megger Test

    Purpose: Measures insulation resistance – quantitative health of the insulation.

    Method: Applies a safe, low-to-medium DC voltage (e.g., 500V, 1000V, 2500V).

    Measurement: Reads resistance (MΩ/GΩ). Higher values = better insulation.

    Outcome: Numeric value (e.g., "200 MΩ"), used for trend analysis.

    Risk: Non-destructive; no discharge needed.

    Use Cases:

    Predictive maintenance (moisture, contamination, aging).

    Troubleshooting insulation degradation.

    Field inspections.


    3.Core Contrasts

    Voltage:

    DC Hipot: High (stress test).

    Megger: Low (diagnostic test).

    Focus:

    DC Hipot: "Will insulation survive a voltage surge?"

    Megger: "How healthy is the insulation?"

    Results:

    DC Hipot: Binary (Pass/Fail).

    Megger: Quantitative (resistance value).

    Safety:

    DC Hipot: Requires post-test discharge (lethal stored energy risk).

    Megger: Safe for routine use.


    También podría gustarte

    • ¡Tiene alguna pregunta!

      NO DUDE EN CONTACTARNOS EN CUALQUIER MOMENTO
      Contáctenos
    • Visítanos

      Edificio 6, Parque Industrial Óptico-Mecánico Optics Valley, 84 Gaoxin 5 Road,
      Zona de desarrollo de nuevas tecnologías de East Lake, ciudad de Wuhan, provincia de Hubei, China

    • Envíanos un correo electrónico

      qiao@hvtest.cc

    • Llámanos

      +86-15871365102